Device Keeps Restarting
Device Keeps Restarting
Symptoms
The Touch One reboots continuously.
Problem
The TouchOne is unable to draw enough current from the Bosch Alarm Panel.
Solution
The Bosch Panel can supply a maximum of 1 Amp current to externally attached devices (Touch One, Keypads, etc)
Should the Touch One not receive enough current it will continue to reboot.
- Install a stand alone power supply for the Touch One Screen. (The Touch one Screen requires a 12v 1A power supply.)